{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
The Lexium ILx runs OK in open loop; in closed the motor keeps stalling.

Possible problem and solution:

Be sure the move profile adjusted to encoder counts when EE=1.
The stall factor (SF) may be to low.
Increase to SF=20.
This will help eliminate nuisance trips.
Depending on the application stall factor, adjustment may be needed based on acceptable position tolerances.


Legacy KB System (APS) Data: RESL200079 V1.0, Originally authored by MaPr on 09/25/2009, Last Edited by MaPr on 09/25/2009
Related ranges: Lexium ILT, ILP

Schneider Electric Nigeria

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: