How can we help you today?

What is the Voltage Insulation for the Optical Isolation on the RS-485 port

Product Line
Powerlogic and ION meters

Environment
Powerlogic
ION


Resolution
The withstand insulation test voltage for optical isolation for the meters are:

6200: 4330 Vrms
73xx: 4330 Vrms
75xx/76xx: 3750 Vrms
7700: 2500 Vrms
8500/8400/8300: 5303 Vrms
8600: 3750 Vrms
8800: 3750 Vrms

Schneider Electric Nigeria

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.