How can we help you today?

What is the purpose of the external battery of the M221?

The help content gives us the information that the battery of the M221 allows:
- to save the content of the whole %MW area ( %MWi with i>50;  note: %MW0-%MW49 are also save without battery)
- to save the RTC clock

In reality the battery is always needed/mandatory because without battery the PLC can’t start in RUN after a Power Cycle.
Within %S75 the PLC program can check when the battery has the be replaced before it becomes out of order (average is every 4/5 years):
=> when this bit is Set to 1, it means the external battery power is low and it has to be replaced soon.