How can we help you today?

What can cause an exception error when trying to connect Modbus TCP on the ATV600 / ATV900 process drives?

Article available in these languages:

Issue:
Unable to connect to ATV600 via Modbus TCP.  Getting "Exception Error" when trying to connect.

Product Line:
ATV600 / ATV900 series process drives.

Environment:
All models, All serial numbers.

Cause:
Unexpected fault condition.

Resolution:
Check that the Unit ID in your Generic Ethernet Module matches the Unit ID of the device you are trying to connect to.

Schneider Electric Nigeria

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales enquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.