ATV320- cannot change AI2 to current

Article available in these languages: Czech

Issue:
Why I cannot change AI2 to current on the ATV320?

Product Line:
ATV320


Environment:
All model numbers, all serial numbers


Cause:
n/a


Resolution:
AI2 is ONLY for voltage ( 0-10 or 0 to +/-10v). For 4-20ma input, suggest to use AI3, set to current (4-20ma).
Then go to CTL menu- set Fr1 to AI3

Schneider Electric Nigeria

ATV320- cannot change AI2 to current

Article available in these languages: Czech

Issue:
Why I cannot change AI2 to current on the ATV320?

Product Line:
ATV320


Environment:
All model numbers, all serial numbers


Cause:
n/a


Resolution:
AI2 is ONLY for voltage ( 0-10 or 0 to +/-10v). For 4-20ma input, suggest to use AI3, set to current (4-20ma). 
Then go to CTL menu- set Fr1 to AI3
 

Schneider Electric Nigeria

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.