How to implement DC braking in the ATV630?
DC injection braking is activated through below parameters

- Stt [Type of stop] = [DC injection] (dCI): DC injection stop ---> when you apply stop command the DC injection braking is active.
Or
- dCI [DC injection assign.] = LI1 to LIx ---> The DC Breaking is activated when you give this assigned Logic input LIx - When you apply this logic input (if assigned) it will apply DC injection breaking.

In addition to the following:
- IdC [DC inject. level 1] = 0.7 In (range 0.1...1.41 In)
- tdI [DC injection time 1] = 0.5 s (range 0.1...30 s)