Why does Control Expert v14.0 generate a linking error when linking a PROCESS section variable to a SAFE section variable?
This error occurs when the customer:
- uses Control Expert 14.0
- loads an already-built application
- adds new variables in a Process section and in a SAFE section
- links the variables
- run a "build change"
Possible workarounds :
- export to .zef format, and reimport
- run a build-all instead of a build-change
This bug was fixed in Control Expert 14.1