{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Why do I have NaN values for PowerTag NSX 3P ?
If you are using a 3P PowerTag NSX on a 3P+N system please check that:
  • you have connected the white wire to the Neutral of your panel
  • the Electrical Network System is defined as 3PH4W under your Smartlink or PowerTag Link Web Interface

Schneider Electric Nigeria

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: