What is the maximum earth fault loop impedance Zs for the TeSys Ultra? What values are taken into consideration to calculate the Zs values?

The charts below detail the earth loop impedance (Zs) for the TeSys Ultra range for any TN system based on BS7671:2008+A3:2015

Two documents are also attached:


1) Zs tables of TeSys motor circuit breakers:

  • TeSys GV2
  • TeSys GV3
  • TeSys GV4
  • TeSys GV7
  • TeSys U

2) Explanation of the calculation of the maximum earth loop impedance. This also includes additional information about:

  • Motor rated devices
  • Ambient temperature


Please refer to the table below which details the maximum earth loop impedance (Zs) for 0.4s disconnection time with Uo 230V

Zs values table for TeSys Ultra

Updated TeSys starter picture - colour change

Schneider Electric Netherlands

Attachment(s)
Tesys Zs Values.pdf [139.87 KB]
Zs v201810.pdf [456.56 KB]