Issue:
Error When Attempting a Runtime Calibration in PowerChute Software
Product Line:
PowerChute Serial Shutdown
PowerChute Business Edition
Environment:
All supported OS
Cause:
1) The battery has less than 100% charge:
2) The load on the UPS is 10% or less:
Resolution:
Two conditions need to be met to perform a calibration:
1) The battery charge needs to be at 100%,
2) The load on the UPS needs to be greater than 10% of the battery capacity
Released for: Schneider Electric Philippines






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.