How can we help you today?

Video: Can the ATV212 default display value be changed from output frequency to another value?

Issue:
Changing the default output value showed on the display.

Product line:
Altivar ATV212

Environment:
All models, all serial numbers

Cause:
Customer preference

Resolution:
Parameter F710 sets the default display.  The factory setting is 0 for motor operating frequency. Other options:
1 = speed reference
2 = motor current
3 = drive rated current
4 = drive thermal state
5 = output power
6 = PID internal speed reference
7 = serial comm data
8 = output speed
9 and 10 are communication frames received data



Schneider Electric Philippines

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings