What is the pulse width of the KY pulse on a Power Meter 800 (PM800) series meter?

Product Line
PM800 Series

Environment
Pulsing

Resolution
The pulse width of the KY pulse on a PM800 is dependant upon the firmware installed.
Prior to fw10.82 the KY pulse was a transition change pulse. With each triggering event the pulse would simply change state.
Figure 1 gives a graphical representation of how a transitional pulse would appear.
Image 1
FW 10.82 and above gives the user the option of choosing to set the KY pulse to transition or pulse.
If the user chooses to set the KY pulse to pulse they can also define the pulse width as 10, 25, 50, 100, 150, 300, 500, or 1000 ms.
Figure 2 gives a graphical representation of how a user defined pulse width would appear.

Image 2
Where t = user defined 10, 25, 50, 100, 150, 300, 500, or 1000 ms.

Schneider Electric Philippines

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings