This is normal when attempting to measure a triac output with no load. Triac outputs cannot be accurately tested without a load.
The high impedance of the voltmeter will introduce enough of a load to cause the applied voltage on the triac to be seen.
Test with a load applied to the triac and you'll get a more meaningful measurement.
R-2202018,
Released for: Schneider Electric Philippines


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.