Is it possible to change application type of my Sepam?

Issue
A new protection application type is need for the existing Sepam.

Product Line
Sepam series 20
Sepam series 40
Sepam series 80

Environment
Application Type

Resolution
The answer is a little bit different according to the Sepam series:

  • ​Sepam series 20 and 40: Modification of Sepam application type requires replacement of your complete Sepam. You need to order a new PowerLogic Protection Relay with the correct application type needed.
  • Sepam series 60 and 80: As application type is in the cartridge, modification of Sepam application type requires only replacement of the cartridge. You need to order a new cartridge with the application type needed. Note: be careful, since you may need to purchase additional CCA63x CT adapters, depending on which Application Types are involved.

Note that in all cases, a firmware patch cannot modify application type of a Sepam.

Update Note (April 2026).

The Sepam 20/40 range is obsolete and has been replaced by the PowerLogic P3 / P5 line, depending on the application. Likewise, the Sepam 60/80 range is in the final stage of its commercial life, and for new projects it can be replaced by the PowerLogic P7.

Schneider Electric Philippines

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings