Can the ION Meter calculate Total demand distortion (TDD)?

Issue

The ION meters calculate Total Harmonic Distortion (THD) by default and the user would like to calculate Total demand distortion (TDD) instead.

Product line

ION 7550/7650, PM8000, ION 8650/8600, ION7330/ION7350, ION9000

Environment
ION Setup 3.0

Resolution
Total demand distortion as defined in the IEEE 519 standard is he total root-sum-square harmonic current distortion, in percent of the maximum demand load current and can be calculated using the following formula:
tdd equation
The IL above is peak or maximum demand load current at the fundamental frequency component measured at the point of common coupling (PCC) derived from the 15 minute or 30 minute billing KVA. With the load already in the system, you can calculate IL as the average of the maximum demand current for the preceding 12 months. for a new installation, you can estimate IL by using predicted load profiles.

One can either setup the ION meter to record the maximum demand current or we can input a calculated value as following:

  1. Navigate the ION meter in advanced mode (ctrl + left click)
  2. Select the 'Maximum Modules' folder and then right click the white space to insert a new module
  3. The source of this new module should be the sliding demand current input as shown below.
    creating a maximum module and linking its input
  4. Change the output register’s name to make it easier to link later on.
  5. Now create maximum modules for I b/ I c current demand accordingly following the same process.
  6. Navigate to Harmonic Measurements Modules and link the Max Demand input each to the output of the maximum module created in step 2.
  7. Do this for each: Ia = I1, Ib = I2, and Ic = I3.
    linking the maximum module to the harmonic measurement module
  8. In the setup tab, change the display mode to “MAGNITUDE OUTPUTS DISPLAYED AS PERCENTAGES“ and the THD display mode to Percentages.

Alternatively, if the IL is to be calculated, one can input a constant using an arithmetic module as following:

  1. Navigate to arithmetic modules and insert a new module
  2. Link Source1 to I a mean from the sliding demand window modules.
  3. In the setup tab, change formula one to the constant calculated in Amps
    arithmetic module in creating the IL value
  4. Change the Output register’s name to make it easier to link.
  5. Navigate to harmonic measurements module and then link the Max Demand input to the output of the arithmetic module created created in step 2
  6. In the setup tab, change the display mode to “MAGNITUDE OUTPUTS DISPLAYED AS PERCENTAGES “ and the THD display mode to Percentages

Schneider Electric Philippines

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:

Need help?

  • Start here!

    Find answers now. Search for a solution on your own, or connect with one of our experts.

  • Contact Support

    Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Search FAQs

    Search topic-related frequently asked questions to find answers you need.

  • Contact Sales

    Start your sales inquiry online and an expert will connect with you.

I'd like to receive news and commercial info from Schneider Electric and its affiliates via electronic communication means such as email, and I agree to the collection of information on the opening and clicks on these emails (using invisible pixels in the images), to measure performance of our communications and improve them. For more details, please read our Privacy Policy.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings