Some of the Sepam 80 protection functions can be used for low-voltage installations, as explained in the Protection Functions User Manual.
However, some of the limitations in terms of supported wiring configurations are not explicitly stated in the user manual.
Also - there are not always warning in SFT2841 to inform the user that a certain configuration is not possible.
Please see the attached file for an example where the 64REF, 51N, and 51G protection functions cannot be achieved using a single Sepam 80 relay. In fact, the protection functions could be applied correctly with a single relay, but some wiring modifications are required.
As explained in the attached file, the key points to keep in mind are as follows:
- for a 4-wire low-voltage system (e.g., TN-C, or TN-S), the CT's used for 51N and 51G should not be the same. They should be installed at different positions.
- all supported configurations for the 64REF function in low-voltage use the CCA634 CT adaptor. So, the corresponding Io input (for the CSH120/200) cannot be used.
- the SFT2841 software (as of version 15.1) does not give any warnings if you create a configuration which enables all of these functions. It is assumed that the project team will check the wiring to ensure that the CSH120/200 (Io) input will not be used if a CCA634 is installed, for example.
AEDL3
However, some of the limitations in terms of supported wiring configurations are not explicitly stated in the user manual.
Also - there are not always warning in SFT2841 to inform the user that a certain configuration is not possible.
Please see the attached file for an example where the 64REF, 51N, and 51G protection functions cannot be achieved using a single Sepam 80 relay. In fact, the protection functions could be applied correctly with a single relay, but some wiring modifications are required.
As explained in the attached file, the key points to keep in mind are as follows:
- for a 4-wire low-voltage system (e.g., TN-C, or TN-S), the CT's used for 51N and 51G should not be the same. They should be installed at different positions.
- all supported configurations for the 64REF function in low-voltage use the CCA634 CT adaptor. So, the corresponding Io input (for the CSH120/200) cannot be used.
- the SFT2841 software (as of version 15.1) does not give any warnings if you create a configuration which enables all of these functions. It is assumed that the project team will check the wiring to ensure that the CSH120/200 (Io) input will not be used if a CCA634 is installed, for example.
AEDL3
Released for: Schneider Electric Philippines
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.