Question:
Could TesysT use unit ID 255 to communicate as a slave with BMENOC03xx
Answer:
No, unity ID 255 is reserved for internal diagnostic. Please use any unit ID among 1~254 to secure the TesysT communication as a slave with BMENOC03xx.
Could TesysT use unit ID 255 to communicate as a slave with BMENOC03xx
Answer:
No, unity ID 255 is reserved for internal diagnostic. Please use any unit ID among 1~254 to secure the TesysT communication as a slave with BMENOC03xx.