Issue:
ATV212 configuration to start and stop from face display and speed up using an external potentiometer?
Product Line:
Altivar 212
Environment:
All
Cause:
Wiring and programming
Resolution:
Wiring for potentiometer:
PP for +10VDC
VIB for signal.
CC for common connection
Programming:
Mode and arrow under AUF.
Set CNOD to 1 for main front display start and stop.
Set FNOD to 2 for 0-10VDC from VIB and CC.
ATV212 configuration to start and stop from face display and speed up using an external potentiometer?
Product Line:
Altivar 212
Environment:
All
Cause:
Wiring and programming
Resolution:
Wiring for potentiometer:
PP for +10VDC
VIB for signal.
CC for common connection
Programming:
Mode and arrow under AUF.
Set CNOD to 1 for main front display start and stop.
Set FNOD to 2 for 0-10VDC from VIB and CC.
Released for:Schneider Electric Philippines