Issue:
ATV630 speed control with local HMI
Product Line:
Altivar ATV600 and ATV900 series drives
Environment:
All
Cause:
The drive's speed is to be controlled by the local HMI
Resolution:
Enter the Main Menu of the Drive. Go to Complete Settings then go to Command and Reference. In this Menu, the first parameter is Ref Freq 1 Config which is set to AI1 (Factory default), change this parameter to Ref Freq-Rmt Ter
Main Menu -> Complete Settings -> Command and Reference
-> HMI CMD to Bumpless (Default is Disabled)
-> Ref Freq 1 Config -> Ref Freq-Rmt Term
-> If Start/Stop from Terminals and Speed control from HMI, Control Mode must be changed to Separate
ATV630 speed control with local HMI
Product Line:
Altivar ATV600 and ATV900 series drives
Environment:
All
Cause:
The drive's speed is to be controlled by the local HMI
Resolution:
Enter the Main Menu of the Drive. Go to Complete Settings then go to Command and Reference. In this Menu, the first parameter is Ref Freq 1 Config which is set to AI1 (Factory default), change this parameter to Ref Freq-Rmt Ter
Main Menu -> Complete Settings -> Command and Reference
-> HMI CMD to Bumpless (Default is Disabled)
-> Ref Freq 1 Config -> Ref Freq-Rmt Term
-> If Start/Stop from Terminals and Speed control from HMI, Control Mode must be changed to Separate
Released for: Schneider Electric Philippines




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.