Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
SBO Struxureware Building Operation (now EBO EcoStruxureâ„¢ Building Operation) WorkStation crashes after value forced
Building Operation Workstation Error window notices:

- A problem has occurred in this application.
More info:
Could not load file or assembly 'SE.Script.Wrapper, Version=1.9.xx...
The system cannot find the file specified.

Cause:
File corrupted or lost

Steps:
1. Check folder : C:\Program Files (x86)\Schneider Electric StruxureWare\Building Operation 1.9\WorkStation\Script...
2. Delete/Rename original corrupted file: SE.Script.Compiler.Wrapper.dll
3. Run WorkStation Installation - Repair current version
4. Start WorkStation

Schneider Electric Philippines

Attachment(s)
WS_installation_repaired.PNG.png [112.95 KB]
Workstation_Script_folder.PNG.png [83.55 KB]
WS_crashinfo_ValueForced.PNG.png [157.81 KB]
WS_installation_repair.PNG.png [85.92 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings