What is the selection criterion of Circuit Breakers for the Capacitor bank application.

The selection should be done after derating the Circuit Breaker taking into consideration voltage variation and capacitors tolerances that could increase nominal current up to 1.5In.
The Derating factor of 1.5In
Where In = Q/ ( Square root of 3 ) Un
Q = Capacitor Power
Un = Nominal Voltage
Choose the Micrologic with delay time selection, so that the Circuit Breaker does not trip due to initial high inrush current.
Also to be taken into account are the parameters like supply frequency, operating voltage & harmonics level of the power system for such application.
Refer the attached sheet for further details for selection of Circuit Breaker for Capacitor duty application.
Note: Use the phase barrier between the phases in Circuit Breaker to prevent flashover due to heavy inrush current.

Schneider Electric Philippines

Attachment(s)
CB_Selection.pdf [256.81 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings