"Configured" status is not displayed in TGML for Cubicle 5 to Cubicle 16 for SMD (Switchgear Monitoring Device)
Issue
"Configured" status is not displayed (checked or unchecked)  in TGML for Cubicle 5 to Cubicle 16 for SMD (Switchgear Monitoring Device)
image.png
Product Line
PO2021 PSO2020 R2 CU1
Environment
PO2021 / PSO2020R2CU1 with webHMI application having SMD devices
Solution
  1. Close any open webHMI application in browser
  2. Stop IIS from IIS Manager
  3. Navigate to C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  4. Take backup of "Thermal" Folder in v2021 folder and its sub-folders (C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021)
  5. Replace the attached (Related) TGML files in Thermal folder normally located at C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  6. If your installation location is different, please make sure you replace these files in Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  7. Start IIS Manager
  8. Open the TGML for SMD and verify the "Configured" Status visible for all Cubicles.
  9. If not able to view updated TGMLs , perform iisreset using Command Prompt (Required Administrator privileges).

Schneider Electric Philippines

Attachment(s)
Thermal tgml files.zip [759.01 KB]
"Configured" status is not displayed in TGML for Cubicle 5 to Cubicle 16 for SMD (Switchgear Monitoring Device)
Issue
"Configured" status is not displayed (checked or unchecked)  in TGML for Cubicle 5 to Cubicle 16 for SMD (Switchgear Monitoring Device)
image.png
Product Line
PO2021 PSO2020 R2 CU1
Environment
PO2021 / PSO2020R2CU1 with webHMI application having SMD devices
Solution
  1. Close any open webHMI application in browser 
  2. Stop IIS from IIS Manager
  3. Navigate to C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  4. Take backup of "Thermal" Folder in v2021 folder and its sub-folders (C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021)
  5. Replace the attached (Related) TGML files in Thermal folder normally located at C:\ProgramData\Schneider Electric\Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  6. If your installation location is different, please make sure you replace these files in Power SCADA Operation\v2021\User\PLS_Include\TGML\Templates\Thermal
  7. Start IIS Manager
  8. Open the TGML for SMD and verify the "Configured" Status visible for all Cubicles.
  9. If not able to view updated TGMLs , perform iisreset using Command Prompt (Required Administrator privileges).

Schneider Electric Philippines

Attachment(s)
Thermal tgml files.zip [759.01 KB]
Explore more
Product:
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product:
Explore more
Product:

Need help?

  • Start here!

    Find answers now. Search for a solution on your own, or connect with one of our experts.

  • Contact Support

    Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Search FAQs

    Search topic-related frequently asked questions to find answers you need.

  • Contact Sales

    Start your sales inquiry online and an expert will connect with you.

I'd like to receive news and commercial info from Schneider Electric and its affiliates via electronic communication means such as email, and I agree to the collection of information on the opening and clicks on these emails (using invisible pixels in the images), to measure performance of our communications and improve them. For more details, please read our Privacy Policy.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.