What are the rules to respect to set BMENOC301/311 (type .2 and .3) IP address configuration for HotStandby system?

Question: What are the rules to respect to set BMENOC301/311 (type .2 and .3) IP address configuration?

Answer: Since version V2.05 on BMENOC301/311, Modbus TCP IOscanning is supported across router. However, since this version, when the gateway IP address is entered, it is expected than MainIP (Main IP+1) AND IP A and IP B to be in the same subnet. Otherwise, Modbus TCP IOscanning will not work correctly.

NOC0301
Configuration 1

Workaround 1 : if IP A and IP B are in a different subnet than Main IP, set a gateway address to 0.0.0.0 will make the IO scanner working correctly.
NOC0301
Configuration 2

Workaround 2 : set IP A and IP B in the same subnet than Main IP will make the IO scanner working correctly.
NOC0301
Configuration 3

Note1 : Starting from version V15.0 , Control Expert DOES NOT allow the gateway address to be configured when Main IP/Main IP+1  and IPA/IPB are in different sub-nets.
NOC0301
Configuration 4


Note2 : In case an application with a BMENOC configured as shown in  "configuration 1" is downloaded into the M580 CPU , depending of the previous BMENOC configuration, the IOscanner may work but only until the NOC module will be rebooted.

Schneider Electric Philippines

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.