Issue:
AFE bus unbalancing or ObF2 fault on the ATV680 Drives.
Product Line:
ATV680 and ATV980 enclosed drives with AFE
Environment:
All 680 and 980 AFE Drives only
Cause:
The Drives internal DC bus voltage is out of range from unsymmetric mains voltage or inoperative AFE Brick.
Resolution:
-Turn off stop and go feature and see if the drive powers up.
-Analysis mains voltage and DC bus voltage.
-Perform visual on the AFE brick (Requires Field Services onsite)
-Replace the AFE brick (Requires Field Services onsite)
Note to turn off stop and go feature from the HMI or keypad.
-Main menu
-My Preferences
-Stop and go
Set to NO
Released for: Schneider Electric Philippines
Issue:
AFE bus unbalancing or ObF2 fault on the ATV680 Drives.
Product Line:
ATV680 and ATV980 enclosed drives with AFE
Environment:
All 680 and 980 AFE Drives only
Cause:
The Drives internal DC bus voltage is out of range from unsymmetric mains voltage or inoperative AFE Brick.
Resolution:
-Turn off stop and go feature and see if the drive powers up.
-Analysis mains voltage and DC bus voltage.
-Perform visual on the AFE brick (Requires Field Services onsite)
-Replace the AFE brick (Requires Field Services onsite)
Note to turn off stop and go feature from the HMI or keypad.
-Main menu
-My Preferences
-Stop and go
Set to NO
Released for: Schneider Electric Philippines








Need help?
Start here!
Find answers now. Search for a solution on your own, or connect with one of our experts.
Contact Support
Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Search FAQs
Search topic-related frequently asked questions to find answers you need.
Contact Sales
Start your sales inquiry online and an expert will connect with you.