Power Monitoring Expert - Adding Offset to the Register Power Monitoring Expert Device Type Editor

Issue:
In PME Device Type Editor, there is no section to add Offset for Modbus Registers.

Product Line:
Power Monitoring Expert 9.0
Power Monitoring Expert 2020

Environment:
Device Type Editor

Cause:
PME 9.0 Device Type Editor does not have the Register Offset column by default in Device Type Editor.

Resolution:
  1. Open Device Type Editor with the desired Driver and Register.
  2. Right click one of the default columns (i.e. Name, Register, Format, ION Handle, Mask, Scal) and select Column Selector.
  3. Scroll to find "Offset" and drag the Offset onto the Column.