Product Line
_____________________________________________________________ 
ION7650
Environment 
_____________________________________________________________ 
ION Setup
PME Designer
Issue 
_____________________________________________________________ 
When reviewing logged data for EN50160 Freq N, Freq N1, and Freq invld, the values will reset twice a year, First at the start of a new year then again at the start of some month. 
Root Cause 
_____________________________________________________________ 
Reset input to Signal limit Evaluation module 1 is pulsed twice in the same year. Logic in the framework is using double "not". 
Solution 
_____________________________________________________________ 
Change the Mode setup register of AND/OR module 11 "PQ Sync Yr Inv".
Default value is NOR, setting should be AND
Released for: Schneider Electric Thailand