Discover Acti9 iPRD
Improve protection and continuity of service of your electrical equipment

The Acti9 iPRD DIN rail Surge Protection Devices (SPD) range is crafted to safeguard your electrical systems and structures from surges caused by indirect lightning strikes. This enhances safety, efficiency, and business operations, particularly in challenging settings. The Acti9 iPRD SPD embodies a sustainable design, facilitating simple maintenance, featuring output dry contacts for remote monitoring. It offers tailored versions for TT, TN-S, TN-C, and IT earthing systems, prolonging the efficiency and lifespan of your equipment.
Benefits
Benefits
Easy to select and install
• Type 2+3 universal products offer wide scope of use in sub and final distribution boards• Compact versions reduce in half space used by device into panelboard• Self-protected versions with embedded backup fuse avoid specific external disconnector• Reduction of cables quantity and complexity• Easier implementation of “50 cm max.” length rule for connection cables
High performance protection
• Voltage protection level (Up) ≤ 1,5kV, offers efficient protection for sensitive loads with overvoltage category I (OVC I)• Maximum discharge current (Imax), up to 65 kA, ensures high discharge capacity in case of indirect lightning strikes• Short-circuit current rating (Isccr), up to 50 kA, enables to withstand high prospective short-circuit fault currents
Continuity of service
• End-of-life remote signaling brings peace of mind and more efficient maintenance• Coordination of integrated backup protection is already certified with declared upstream circuit breakers and fuses disconnectors• Nominal discharge capacity (In), up to 20 kA, ensures better protection longevity
Last novelties in iPRD range
Last novelties in iPRD range
A complete and innovative iPRD range
A complete and innovative iPRD range
Type 2 SPD with pluggable cartridges for buildings at risk of surges from lightning or switching disturbances. Compatible with all neutral systems, fits main or sub-distribution DIN rail panel boards. They are not self-sufficient to protect sensitive loads placed at more than 10m and should be completed downstream with Type 3 SPD.• (Imax) maximum discharge current = 20 kA (iPRD 20) / 40 kA (iPRD 40) / 65 kA (iPRD 65).• (In) nominal discharge current = 5 kA (iPRD 20) / 15 kA (iPRD) 40 / 20 kA (iPRD 65).• (Up) Voltage protection level: N-PE ≤ 1.4 kV & L-N ≤ 1,2 kV (iPRD 20) / 1,6 kV (iPRD 40) / 1,5 kV (iPRD 65).• (Isccr) short-circuit current rating ≤ 50 kA.• (Uc) maximum continuous operating voltage = 350 Vac (L-N).
Applications
Applications
Residential
Explore moreCommercial buildings
Explore moreIndustry
Explore more