Hot Fix ControlExpert_V140_HF0537032R_Multi_Packet_Management is now included in ControlExpert_V140_HF2, available at : https://www.se.com/ww/en/download/document/ControlExpert_V140_HF2/ Description of issue or behavior (before installation of ControlExpert_V140_HF0537032R) On M580 PLC: During online modification the Progress Bar doesn’t display correctly: progress is not accurate (go back, and go forward, and go back etc… before reaching full Completion) after online modification is applied in the PLC (with PLC in RUN), the PLC may go in HALT or stop working. New behavior after installation of ControlExpert_V140_HF0537032R On line modification behaves OK.