{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Can you provide the Earth fault loop impedance (Zs) for the Domae MCBs?

Please find the list of Domae MCB's Earth fault loop impedance Zs values. In order to comply with BS7671 Amendment 3: 2015 the figure in attachment should be multiplied with C min .95

Please note this is now discontinued, for legacy info only

Schneider Electric UK

Attachment(s)
TRIP curve Zs DOM.pdf [11.12 KB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Product: