Issue:
Customers need to correctly identify a 'U-space' or 'rack space.'
Product Line:
NetShelter SX
Environment:
All versions and serial ranges.
Cause:
Incorrect placement of equipment can create airflow problems, like hot air recirculation.
Resolution: see below
As set forth by the EIA/ECA-310-E Standard:
1. For any Rackmount device or enclosure - a U or unit of rack space is equivalent to 1.75 inches or 44.45 mm.
2. The mounting hole pattern on a rack or enclosure must follow the following guideline:
EIA/ECA-310-E rail specifications in attached file.
To properly mount a device in the rack, a user needs to utilize the notched square mounting hole to indicate the center of a U space. For Example, to mount a 1 U device, 3 mounting holes would be covered by the device with the notched hole residing in the center of the group of 3. Mounting in an "off-U position", effectively moving the installed device 1 hole space up or down is incorrect and will lead to airflow and cooling issues.
Customers need to correctly identify a 'U-space' or 'rack space.'
Product Line:
NetShelter SX
Environment:
All versions and serial ranges.
Cause:
Incorrect placement of equipment can create airflow problems, like hot air recirculation.
Resolution: see below
As set forth by the EIA/ECA-310-E Standard:
1. For any Rackmount device or enclosure - a U or unit of rack space is equivalent to 1.75 inches or 44.45 mm.
2. The mounting hole pattern on a rack or enclosure must follow the following guideline:
- Vertical Hole spacing must follow a pattern of 5/8""-5/8""-1/2"" or 15.9mm-15.9mm-12.7mm
- Horizontal Hole spacing must be 18.3"" or 465 mm (+/- 1.6 mm)
- Clearance between inner edges of mounting rails must be 450 mm at minimum
- Outside edges of mounting rail must be 483.4 mm apart at minimum
EIA/ECA-310-E rail specifications in attached file.
To properly mount a device in the rack, a user needs to utilize the notched square mounting hole to indicate the center of a U space. For Example, to mount a 1 U device, 3 mounting holes would be covered by the device with the notched hole residing in the center of the group of 3. Mounting in an "off-U position", effectively moving the installed device 1 hole space up or down is incorrect and will lead to airflow and cooling issues.
Released for: Schneider Electric Vietnam










Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.