Issue:
Customers require information on grounding NetShelter cabinets to IEC specifications.
Product Line:
NetShelter SX
Environment:
All versions and serial ranges.
Cause:
This installation requires grounding per IEC specifications.
Resolution :
NetShelter SX cabinets are UL Listed and have all metal components grounded per UL/IEC 60950 requirements and meet the 0.1 ohm resistance.
Equipment to be installed in a NetShelter SX cabinet should be Listed equipment.
Installation of any unlisted or recognized components requires a safety review of the completed assembly.
Customers require information on grounding NetShelter cabinets to IEC specifications.
Product Line:
NetShelter SX
Environment:
All versions and serial ranges.
Cause:
This installation requires grounding per IEC specifications.
Resolution :
NetShelter SX cabinets are UL Listed and have all metal components grounded per UL/IEC 60950 requirements and meet the 0.1 ohm resistance.
Equipment to be installed in a NetShelter SX cabinet should be Listed equipment.
Installation of any unlisted or recognized components requires a safety review of the completed assembly.
Released for: Schneider Electric Vietnam




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.