Issue:
Setting up the ATV21 and ATV212 drives for a 4 to 20mA loss of follower.
Product Line:
Altivar ATV21 and ATV212 drive.
Environment:
All
Cause:
They want to get the drive to fall back to a fixed speed if the 4 to 20mA signal is loss.
Resolution:
Press MODE and hold the arrow down to F----- and press enter
F633= Loss of VA set to any value above 0%

F644= 4-20mA loss behavior
F649=Fallback speed set point in hz.

See the programming manual https://www.se.com/us/en/download/document/S1A53838/ for more information.
Setting up the ATV21 and ATV212 drives for a 4 to 20mA loss of follower.
Product Line:
Altivar ATV21 and ATV212 drive.
Environment:
All
Cause:
They want to get the drive to fall back to a fixed speed if the 4 to 20mA signal is loss.
Resolution:
Press MODE and hold the arrow down to F----- and press enter
F633= Loss of VA set to any value above 0%
F644= 4-20mA loss behavior
F649=Fallback speed set point in hz.
See the programming manual https://www.se.com/us/en/download/document/S1A53838/ for more information.
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.