How to increase the update rate for the Position Actual Value on Lexium 28 with CANopen
Issue
I want to increase the update rate of CANopen PDOs including the Position Actual Value on a Lexium 28 from the default 100ms.

Product Line
Lexium 28 with CANopen
EcoStruxure Machine Expert


Environment
PLC Programming software in Windows - Logic Builder

Resolution

Prerequisite:
The PDO parameters Statusword and Position Actual Value are both enabled with the checkbox in the Transmit PDOs:
Transmit PDOs - Enable 16#1801


To increase the update rate of the CANopen Positional Actual Value on a Lexium 28, follow these steps:
1) In the EcoStruxure Machine Expert Logic Builder, go to the Devices Tree
2) Expand the CANopen bus -> CANopen_Performance nodes to find the Lexium_28 device node
3) Double-click on the Lexium_28 node you wish to edit
4) Click on the CANopen Parameters tab
5)  Scroll down to the PDOs -> TxPDOs ->
6) Expand TxPDOs -> available TxPDOs -> PDO 16#1801 -> PDO 16#1801 -> available PDO-Parameter
The sending of the Position Actual Value" TxPDO from the Lexium, by default is every 100ms by internal timer here.
CANopen Parameters tab for Lexium 28
7)  Set the Event Timer to your desired transmit time from the Lexium 28
NOTE: Practically, 15ms is the fastest value for the Lexium 28

Optional

If you need these status variables faster than 100ms:
driveStat
mfStat
motionStat
driveInput

1) Expand TxPDOs-> available TxPDOs -> PDO 16#1800 -> PDO 16#1800 -> available PDO-Parameter
2) Set the Inhibit Time to 20ms

Event Timer is the set interval time you wish a TxPDO to be transmitted at from the Lexium (or other CANopen device)
Inhibit Time prevents sending of a TxPDO message regardless of the Event Timer Time. Useful for if you've already set an Event Timer time and you're tuning for network bandwidth if you have many drives or I/O.

Schneider Electric Vietnam

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
How to increase the update rate for the Position Actual Value on Lexium 28 with CANopen
Issue
I want to increase the update rate of CANopen PDOs including the Position Actual Value on a Lexium 28 from the default 100ms.
 
Product Line
Lexium 28 with CANopen
EcoStruxure Machine Expert

 
Environment
PLC Programming software in Windows - Logic Builder
 
Resolution
 
Prerequisite:
The PDO parameters Statusword and Position Actual Value are both enabled with the checkbox in the Transmit PDOs:
Transmit PDOs - Enable 16#1801
 
 
To increase the update rate of the CANopen Positional Actual Value on a Lexium 28, follow these steps:
1) In the EcoStruxure Machine Expert Logic Builder, go to the Devices Tree
2) Expand the CANopen bus -> CANopen_Performance nodes to find the Lexium_28 device node
3) Double-click on the Lexium_28 node you wish to edit
4) Click on the CANopen Parameters tab
5)  Scroll down to the PDOs -> TxPDOs ->
6) Expand TxPDOs -> available TxPDOs -> PDO 16#1801 -> PDO 16#1801 -> available PDO-Parameter
The sending of the Position Actual Value" TxPDO from the Lexium, by default is every 100ms by internal timer here.
CANopen Parameters tab for Lexium 28
7)  Set the Event Timer to your desired transmit time from the Lexium 28
NOTE: Practically, 15ms is the fastest value for the Lexium 28
 
Optional

If you need these status variables faster than 100ms:
driveStat
mfStat
motionStat
driveInput
 
1) Expand TxPDOs-> available TxPDOs -> PDO 16#1800 -> PDO 16#1800 -> available PDO-Parameter
2) Set the Inhibit Time to 20ms
 
Event Timer is the set interval time you wish a TxPDO to be transmitted at from the Lexium (or other CANopen device)
Inhibit Time prevents sending of a TxPDO message regardless of the Event Timer Time. Useful for if you've already set an Event Timer time and you're tuning for network bandwidth if you have many drives or I/O.
 

Schneider Electric Vietnam

Explore more
Product:
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Explore more
Product:

Need help?

  • Start here!

    Find answers now. Search for a solution on your own, or connect with one of our experts.

  • Contact Support

    Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Search FAQs

    Search topic-related frequently asked questions to find answers you need.

  • Contact Sales

    Start your sales inquiry online and an expert will connect with you.

I'd like to receive news and commercial info from Schneider Electric and its affiliates via electronic communication means such as email, and I agree to the collection of information on the opening and clicks on these emails (using invisible pixels in the images), to measure performance of our communications and improve them. For more details, please read our Privacy Policy.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.