Issue:
General principles and guidelines on air intakes and outlets
Product line:
All Air removal equipment
Environment:
All Product models, all serial numbers
Cause:
Pressure issues that can occur from improper balance
Resolution:
Air Intakes and Outlets
Ventilation systems - air intakes and outlets and rules of thumbs
Intakes
- Intakes should be at least 0.15 m (0.5 ft) above the terrain. In areas with traffic the intake should be at least 5 m (16 ft) above the terrain.
- The distance between intake, firewalls, and surrounding buildings must be according the rules of the local authorities.
- Short cutting intake air with used outlet air must be avoided.
- An air intake should be located in a position where the wind influence on the pressure conditions within the system is limited.
- Air velocities in the intake openings should not exceed 2.5 m/s (~ 500 ft/min)
Outlets
- Outlets should go direct out in unrestricted area.
- Short cuts with intake air, window openings and residence areas must be avoided.
- The distance between outlet, firewalls and surrounding buildings must be according the rules of the local authorities.
- An air outlet should be located in a position where the wind influence on the pressure conditions within the system is limited.
- The air velocity through the outlet should not exceed 3 - 15 m/s (~ 500 - 3000 ft/min).
Đã phát hành cho: Schneider Electric Việt Nam
Bạn cần trợ giúp?
Công cụ chọn sản phẩm
Nhanh chóng và dễ dàng tìm được sản phẩm và phụ kiện phù hợp cho các ứng dụng của bạn.
Nhận báo giá
Bắt đầu gửi yêu cầu bán hàng trực tuyến và chuyên gia sẽ liên hệ với bạn.
Nơi mua hàng?
Dễ dàng tìm nhà phân phối Schneider Electric gần bạn nhất.
Trung tâm Hỗ trợ
Tìm sự hỗ trợ cho mọi nhu cầu của bạn tại một nơi.