{}

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric corporate Website

Search FAQs
How Unity Pro application can be restored from SD memory card to a CPU?
A Unity Pro application can be restored from SD memory card to Modicon PLC CPU like M580 and M340.

1- Switch off the PLC
2- Insert the SDCard "where the application saved in" into the CPU
3- Switch on the PLC
Let the PLC for few moments till the application is being transferred to the CPU.

Schneider Electric Global

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: