Issue:
Customer wants to have R1 close when motor frequency reaches the reference frequency.
Product Line:
Altivar ATV600 and ATV900
Environment:
All serial numbers
Cause:
Customer set up R1 frequency reference attained.
Resolution:
Check R1 assignment under Complete Settings -> Input/output -> Relay -> R1 Configuration -> R1 assignment -> [Ref Freq Reached] SrA or Frequency reference reached.
R1A and R1C will close at and above Frequency reference.
Customer wants to have R1 close when motor frequency reaches the reference frequency.
Product Line:
Altivar ATV600 and ATV900
Environment:
All serial numbers
Cause:
Customer set up R1 frequency reference attained.
Resolution:
Check R1 assignment under Complete Settings -> Input/output -> Relay -> R1 Configuration -> R1 assignment -> [Ref Freq Reached] SrA or Frequency reference reached.
R1A and R1C will close at and above Frequency reference.
Released for:Schneider Electric Global

