{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
The ATV312 has +24Vdc on logic inputs where no wires are connected?
Issue:
ATV312 measuring +24Vdc with no wires on logic inputs.

Product Line:
ATV312

Environment:
All

Cause:
Expecting 0Vdc on the logic inputs until 24Vdc is applied to them.

Resolution:
The Sink / Source switch needs to be in the source position for active high logic input operation.

Schneider Electric South Africa

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: