In order to select the proper indoor type voltage transformer for an application we need to define customer requirements based on the primary circuit and the metering and protection chains; i.e. define customer requirements in terms of voltage transformer specifications, key specifications can be summarized as follows:
- Rated primary voltage(s) or insulation level Ur/Ud/Ui in kV.
- Rated secondary voltage(s).
- Rated frequency (e.g. 50 or 60Hz).
- Earthing system (isolated or not).
- Desired accuracy class in measurement chain (e.g. class 1, 0.5 …etc).
- Desired rated burden (in VA) for measurement chain (e.g. 25VA).
- Desired accuracy class in protection chain (e.g. class 3P, 6P …etc).
- Desired rated burden (in VA) for protection chain (e.g. 25VA).
- Special requirements such as out-of-standard temperature/environment/altitude; connections; terminal covers; etc