Micom P546 relay is not able to send MCL & cannot be read from front and rear port through Easergy studio.Can you suggest the suitable solution to solve this issue?
Please check the below points to solve this issue :
1)    We suggest to use mcl file from the configurator tool directly
2)    Please use the latest Easergy studio from our Schneider website (https://www.se.com/ww/en/product-range-presentation/61035-easergy-studio)
3)    Please disable the read only check the same under configuration & they need to check whether ready only is disable.