{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Micom P632 relay is displaying “SFMON: Wrong module Dig.Bus” error .What is the meaning of this error ?

The device has been fitted with a wrong digital bus. Since this is checked using the module variant number this signal can also occur after a firmware
upgrade to a version that is not compatible with the hardware.

1st device reaction with Warm restart & 2nd device reaction will be blocking.

If device is block permanent, please contact our local after sales team to rectify the same.

Schneider Electric South Africa

Explore more
Range:
Easergy MiCOM P63x Protection Relays
Explore more
Range:
Easergy MiCOM P63x Protection Relays
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.