Can Micom P143 carry out Remnant Undervoltage protection function (ANSI 27R) / Anti-backspin?

Issue:
having ANSI 27R in MICOM P143

Environment;
MICOM protection functions

Resolution:
Micom P143 can not carry out Remanent Undervoltage protection function (ANSI 27R)/Anti-backspin. To have this protection function,the relay settings for Voltage Transformer (VT) connection must have the option ( 2VT + Remanent ) .
As seen in the below screenshots from Easergy studio, this option is available in MICOM P24x (Motor application) settings but not in P143.

image 1
Also the below logic of the protection function exists in MICOM P24x but not in P143;

image 2