Video: Replacing the Intelligence Module in Smart‑UPS Modular Ultra 5–20 kW
Issue:
The UPS reports an intelligence module fault, communication issue or requires replacement of the intelligence module as part of troubleshooting or maintenance.
Product Line:
APC Smart‑UPS Modular Ultra 5 kW, 10 kW, 15 kW, and 20 kW
Environment:
UPS Models that begin with SRYL5K up to SRYL20K
All Serial Numbers
Cause:
The intelligence module may need replacement due to hardware failure, communication errors, or as part of service maintenance.
Resolution:
The Smart‑UPS Modular Ultra uses user-replaceable Intelligence Module part number: SRYLIM.
It is hot‑swappable when replaced one at a time without shutting down the UPS.
NOTE: Do not remove both Intelligence Modules from the UPS frame at the same time. The UPS will drop the connected load.
Intelligence Module Replacement Steps:
- Remove the front bezel located beside the display.
- Loosen the thumb screw, then slide it to the left to release the module.
- Pull the intelligence module out of the UPS.
- Slide the replacement intelligence module fully into the slot.
- Tighten the thumb screw to secure the new module.
- Reinstall the front bezel.
For a visual guide, please refer to the replacement video below.
If you have any questions or need further assistance, please get in touch with our customer care center at https://www.se.com/us/en/work/support/.
Released for: Schneider Electric South Africa
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.