Does the Modbus Cradle Communication Module (CCM) support 2 wire RS485 communications?

Published date: 14 May 2020

Issue:
User may need to connect the CCM to a 2 wire daisy chain.

Product Line:
Cradle Communication Module 

Environment:
RS-485 Communications

Resolution:
The Modbus Cradle Communications Module does support 2 wire RS485 communications. The module can be configured by jumpering the IN+ and the OUT+ and the IN- and the OUT-.
 