Can I use a different line voltage than what my drive is rated for?

Published date: 19 June 2020

Issue:
Different line voltage usage for Altivar Drives 
 
Product Line:
Altivar drives
 
Environment:
All models 
 
Cause:
None
 
Resolution:
Drives that are rated for a specific line voltage range should only be operated within that range. Attempting to operate a drive outside this range will result in an under supply fault or over supply fault.
Line voltage tolerance is +10% and -15%.

For example: With a 460V drive the line voltage tolerance range would be 391VAC to 506VAC. 
 