How do I get the standby CPU to run automatically after program transfer?
Issue
Automatically run standby CPU after the transfer of the program
Product Line
M580
Environment
EcoStruxure Control Expert
Resolution
To have the standby CPU run automatically after a transfer, you need to set the CMD_RUN_AFTER_TRANSFER bit before you transfer to the standby controller. You can set this in an animation table, or you could hard-code this bit to always be true in your first section of logic.