2 x MTZ Circuit Breakers that we are mechanically interlocking with Cables (LV847926SP & LV833209SP), can we also fit LV848614SP?

Product:

MTZ Breaker

Solution:

Mechanical interlock and door interlock cannot be implemented simultaneously, because they use the same position to install the pin to realize the tripping of breaker.

Mechanical interlock:

Image 1

Door interlock

Image 2

Also please see this snippet from MTZ catalogue:

Image 3