As per the requirement given above, the VFD will be used only for smooth starting and stopping of the pump. The VFD is not used with pump continuously for energy saving purpose.
It is not recommended to use VFD for the above functional requirement of start and bypass application, because when bypass contactor is ON, the 3 phase input power supply will be connected directly to the drive output through bypass contactor. If input supply is directly connected to the output of VFD, it will damage the IGBT's of the VFD. Refer the highlighted warning screen shot below from ATV61 VFD installation manual.
To avoid direct line supply to VFD output, if we disconnect the VFD output contactor after acceleration to full speed from VFD and command (switch ON) the bypass contactor, it will lead to power disconnection to motor for 1 sec, hence there will be drop in motor speed and hammering effect during change over from VFD to Bypass. Hence this operation with VFD is not recommended.
However ATS48 soft starter can be used to comply the above functional requirement. The customer can use ATS48 soft starter with the control scheme screen shot attached below
It is not recommended to use VFD for the above functional requirement of start and bypass application, because when bypass contactor is ON, the 3 phase input power supply will be connected directly to the drive output through bypass contactor. If input supply is directly connected to the output of VFD, it will damage the IGBT's of the VFD. Refer the highlighted warning screen shot below from ATV61 VFD installation manual.
To avoid direct line supply to VFD output, if we disconnect the VFD output contactor after acceleration to full speed from VFD and command (switch ON) the bypass contactor, it will lead to power disconnection to motor for 1 sec, hence there will be drop in motor speed and hammering effect during change over from VFD to Bypass. Hence this operation with VFD is not recommended.
However ATS48 soft starter can be used to comply the above functional requirement. The customer can use ATS48 soft starter with the control scheme screen shot attached below
Publié pour: Schneider Electric Belgium










Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.