Issue 
The Schneider Electric CoreServiceHost service needs to connect to PowerSCADA Runtime through a valid Username/Password (defined in PowerSCADA project) and Citect I/O Server IP Address. 
Product Line 
PowerSCADA Expert 8.1 
Environment 
Windows Services 
Application Configuration Utility 
Cause 
A change in server IP address or removing the 'user' defined in PowerSCADA Project.  The status of the Schneider Electric CoreServiceHost service will continue to show as 'running', however, it is not connecting to PowerSCADA Runtime. 
Resolution 
Open a browser and type the following for the URL:   http://localhost:23103/CoreServiceHost/Alarms/AlarmProxy/status 
When a connection can be made, the following message is returned:  
When a connection cannot be made, the following message is returned:  
Note: In the latter case, the problem can further be investigated in Application Configuration Utility by checking the Username/Password and server IP Address.