How to Test Schneider Electric CoreServiceHost
Issue
The Schneider Electric CoreServiceHost service needs to connect to PowerSCADA Runtime through a valid Username/Password (defined in PowerSCADA project) and Citect I/O Server IP Address.
Product Line
PowerSCADA Expert 8.1
Environment
Windows Services
Application Configuration Utility
Cause
A change in server IP address or removing the 'user' defined in PowerSCADA Project. The status of the Schneider Electric CoreServiceHost service will continue to show as 'running', however, it is not connecting to PowerSCADA Runtime.
Resolution
Open a browser and type the following for the URL: http://localhost:23103/CoreServiceHost/Alarms/AlarmProxy/status
When a connection can be made, the following message is returned:
When a connection cannot be made, the following message is returned:
Note: In the latter case, the problem can further be investigated in Application Configuration Utility by checking the Username/Password and server IP Address.
Publié pour: Schneider Electric CoreServiceHost | Schneider Electric Belgium




Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.