What is the recommended separation of power wiring from communication cables for the Altivar AC Drives?
Issue:
What is the recommended separation of power wiring from communication cables?

Product Line:
Altivar drives

Environment:
All

Cause:
Installation question

Resolution:
A minimum of 12 inches of separation.